Item #1: Garage Fan Coils — Cleaning Required YELLOW - Recommended
| Location | Status | Notes |
|---|---|---|
| Garage Level 1 — Above Spot 30 and Throughout | Needs Cleaning | Four fan coils were identified within the lower level garage that require cleaning. Coils are visibly dirty with debris buildup. Fan coils should be cleaned twice a year and washed down to maintain performance. Recommend scheduling immediate cleaning and establishing a bi-annual preventative maintenance schedule. Refer to inspection photos for this item. |
Item #2: Garage Door Heater Coils — Cleaning Required YELLOW - Recommended
| Location | Status | Notes |
|---|---|---|
| Garage Level 1 — Near Garage Door Entry | Needs Cleaning | Heater coils near the garage door entry are dirty and require cleaning. Coils should be cleaned as part of regular preventative maintenance to ensure proper heating during cold months. Recommend cleaning and adding to the quarterly PM schedule. |
Item #3: Mechanical Penthouse — Boiler System GREEN - Good
| Location | Status | Notes |
|---|---|---|
| Eighth Floor — Mechanical Penthouse | Good | Two-pipe boiler heating system serviced by Northland Mechanical. No signs of any active issues. No boiler logs were found on site — recommend verifying that a boiler log is maintained. Refer to inspection photos. |
Item #4: Mechanical Penthouse — Radon System YELLOW - Recommended
| Location | Status | Notes |
|---|---|---|
| Eighth Floor — Mechanical Penthouse | Needs Inspection | A radon mitigation system is installed, with an installation date of January 28, 2020. No recent service or inspection documentation was observed. Recommend having the radon system inspected and serviced to confirm it is operating correctly. Refer to inspection photos. |
Item #5: Mechanical Penthouse — Cooling Tower and Chemical Feed System YELLOW - Recommended
| Location | Status | Notes |
|---|---|---|
| Eighth Floor — Mechanical Penthouse / Rooftop | Needs Cleaning | The cooling tower is currently off for the season. The chemical feed station for the cooling tower is in place. The cooling tower external filter cages need to be cleaned, and some are missing. The float appears to be in rough condition and should be replaced. The cooling tower itself could use a cleaning. Model and serial number plates were documented via photos. Cooling tower water testing logs were present on site. Recommend cleaning the cooling tower, replacing missing filter cages, installing a new float, and considering installation of thick mesh screening on intakes to prevent cottonwood and debris from entering the system. Refer to inspection photos. |
Item #6: Mechanical Penthouse — Cooling Tower Fan VFD GREEN - Good
| Location | Status | Notes |
|---|---|---|
| Eighth Floor — Mechanical Penthouse | Good | Cooling tower fan VFD appears to be in working order with no error codes present. Currently out of cooling season. No action required. |
Item #7: Rooftop HVAC Unit (Aeon) — Filters Need Immediate Replacement RED - Essential
| Location | Status | Notes |
|---|---|---|
| Rooftop — Aeon Rooftop Unit | Needs Replacement | The Aeon rooftop HVAC unit filters are in extremely poor condition and require immediate replacement. Filter sizes are 24x24x4 and 24x24x2. The filters are deteriorating to the point where debris will be sucked into the unit if not addressed promptly. Recommend immediate filter replacement and establishing a quarterly filter change schedule. Additionally, recommend installing thick mesh screening on the intake to help keep cottonwood and other debris out between filter changes. Refer to inspection photos for this item. |
Item #8: Retail Space — Air Handler Filters YELLOW - Recommended
| Location | Status | Notes |
|---|---|---|
| First Floor — Retail Space | Needs Replacement | Air handler filters in the retail space need to be changed. Recommend changing air filters quarterly as part of preventative maintenance, even if the retail space is not currently occupied. Maintaining air quality and HVAC efficiency is important regardless of occupancy status. |
Item #9: Rooftop — Panasonic Converter Unit YELLOW - Recommended
| Location | Status | Notes |
|---|---|---|
| Rooftop | Needs Cleaning | A Panasonic converter unit is located on the rooftop and needs to be cleaned as part of preventative maintenance. Recommend adding to the regular PM cleaning schedule. Refer to inspection photos. |
Item #10: Garage 2 — Heater Coils Need Cleaning YELLOW - Recommended
| Location | Status | Notes |
|---|---|---|
| Main Level — Garage 2 | Needs Cleaning | Three heater coils were identified in garage 2 that require cleaning. Recommend cleaning all heater coils and adding to the bi-annual preventative maintenance schedule. Refer to inspection photos. |
Item #11: Garage 2 — Air Handler Filters Need Replacement YELLOW - Recommended
| Location | Status | Notes |
|---|---|---|
| Main Level — Garage 2 | Needs Replacement | The garage 2 air handler filters need to be changed. The air handler is mounted high and requires a ladder to access. There are also filters stored on top of the air handler that need to be removed and stored elsewhere. An additional air handler on the west side of garage 2 also needs filter replacement. Recommend replacing all filters and establishing a quarterly filter change schedule. Refer to inspection photos. |
Item #12: Garage 2 — Vent Cleaning Required YELLOW - Recommended
| Location | Status | Notes |
|---|---|---|
| Main Level — Garage 2 | Needs Cleaning | Vents within garage 2 are very dirty and need a thorough cleaning. Recommend cleaning as part of general garage maintenance and adding to the quarterly PM schedule. |
Item #13: Entry Vestibule — Heater Making Ticking Noise YELLOW - Recommended
| Location | Status | Notes |
|---|---|---|
| First Floor — Entry Vestibule | Needs Inspection | The heater in the entry vestibule is working but making a ticking noise. Thermostat covers are also open in this area. Recommend having the heater inspected to identify the source of the ticking noise and closing or replacing the thermostat covers. Refer to inspection photos. |